NEC Article 220 · 2026 NEC

NEC Article 220 is now Article 120

In the 2026 NEC, the branch circuit, feeder and service load calculation rules moved from Article 220 to new Article 120. Most sections keep their number after the article, so 220.82 is now 120.82, but a few moved and some figures changed: the minimum unit load for feeders and services is now 2 VA per square foot, and 120.82 takes the first 8 kVA at 100 percent instead of 10 kVA.

What changed, not just the number

How the Annex D examples changed

The worked examples in Informative Annex D use the new figures, so their answers changed.

Example2023 NEC2026 NEC
D1(a)78 A, 61 A neutral (3 VA per square foot); 100 A service75 A, 58 A neutral (2 VA per square foot for the feeder); 100 A service
D1(b)99, 84 and 104 A; 110 A service96, 81 and 101 A; 110 A service
D2(a)90 A (first 10 kVA at 100 percent, 3 VA per square foot); 100 A service82 A (first 8 kVA at 100 percent, 2 VA per square foot); 100 A service
D2(b)122 A114 A
D2(c)34,790 VA = 145 A; 150 A service permitted32,790 VA = 137 A; 150 A service permitted
D330,320 VA = 126 A; 1 AWG copper; 150 A OCPD32,600 VA = 136 A; 1/0 AWG copper; 150 A OCPD
D4(a)273 A and 434 A249 A and 399 A
D4(b)697 A and 1028 A (factors 0.38 and 0.28, Table 220.84(B))671 A and 988 A (factors 0.38 and 0.28, Table 120.84(C))
D5(a)208 A and 313 A192 A and 289 A
D5(b)685 A (reuses the single-phase 40-unit factor of 0.28)711 A (equivalent count of 28 dwelling units under 120.84(A)(2), factor 0.33)

Worked example: the 2 VA per square foot load

The general lighting load covers all general lighting and the general-use receptacles in a dwelling. You do not count outlets; you multiply floor area by a unit load.

Where to look
Article 120 Part III, 120.41: 2 VA per ft² (22 VA/m²) for one-family, two-family and multifamily dwellings. It already includes the general-use receptacles (including bathroom and garage circuits), the outdoor and basement receptacles, and the required lighting outlets.

2026 trap
New 120.13 uses 3 VA/ft², but only to count how many lighting branch circuits are needed. The feeder and service figure in 120.41 is 2 VA/ft². Some 2023-edition material uses 3 VA/ft² for the service; for the 2026 exam, use 2.

Procedure

  1. Find the floor area by 120.5(C).
  2. Multiply by 2 VA/ft² (or 22 VA/m² for metric areas).

Worked example
A 1,650 ft² ranch home.

Most common mistake
Using 3 VA/ft² for a service calculation, or using the ft² value on an area given in m². Also do not add separate loads for ordinary receptacles; 120.41 already includes them.

The full residential load calculation, with practice questions

Article 220 to Article 120, section by section

2023 NEC2026 NEC
220.1120.1
220.3120.4
220.5120.5
220.10120.10
220.11120.11
220.14120.14
220.16120.16
220.40120.40
220.41120.41
220.42120.42
220.43120.43
220.44120.44
220.45120.45
220.46120.46
220.47120.47
220.50120.50
220.51120.51
220.52120.52
220.53120.53
220.54120.54
220.55120.55
220.57120.57
220.60120.6
220.61120.61(A)
220.70120.7
220.80120.80
220.82120.82
220.83120.83
220.84120.84
220.85120.85
220.86120.86
220.87120.87
220.88120.88
220.100120.100
220.102120.102
220.103120.103
220.120120.120
Table 220.42(A)Table 120.42(A)
Table 220.45Table 120.45
Table 220.47Table 120.47
Table 220.54Table 120.54
Table 220.55Table 120.55
Table 220.56Table 120.56
Table 220.83(A)Table 120.83
Table 220.83(B)Table 120.83
Table 220.84(B)Table 120.84(C)
Table 220.86Table 120.86
Table 220.88Table 120.88
Table 220.102(B)Table 120.102(B)
Table 220.103Table 120.103
Table 220.120Table 120.120

Common questions

Is Article 220 still in the 2026 NEC?

No. The load calculation rules that were Article 220 in the 2023 NEC are Article 120 in the 2026 NEC. Most sections keep their number after the article, so 220.82 is 120.82.

Which Article 220 should I study?

The one your exam tests. A 2023 NEC exam (Oklahoma and many other states) still uses Article 220; a 2026 NEC exam (Texas since September 1, 2026) uses Article 120.

Next step

Last verified November 11, 2026.