Free calculator · 2026 and 2023 NEC
Conduit Fill Calculator
Choose the conduit and list the conductors, mixed sizes and insulation types included, and get the fill percent and the smallest trade size that holds them, from NEC Chapter 9, Tables 1, 4 and 5, with the arithmetic shown.
1/2 in. smallest EMT for these conductors
Same-size count: up to 9 of these conductors fit in 1/2 in. EMT, rounding up a remainder of 0.8 or more (Chapter 9, Note 7).
How it was worked out
- 4 × 12 AWG THHN / THWN-2: 0.0133 in² each (Chapter 9, Table 5) = 0.0532 in²
- Total: 4 conductors, 0.0532 in².
- Allowed fill: more than two conductors may fill 40 percent of the conduit's internal area (Chapter 9, Table 1).
- Smallest EMT whose 40% area is at least 0.0532 in²: trade size 1/2 (0.122 in², 17.5% full).
Code sections (2026 NEC): Chapter 9, Table 1; Chapter 9, Table 4; Chapter 9, Table 5; Chapter 9, Notes to Tables.
Practice this on exam-style questions
Conduit fill questions are a standard part of the journeyman exam. Practice them in a free practice test for your state.
AmpPrep courses teach conduit fill for each state's journeyman exam, with lessons, review and timed practice exams. Find your state's exam.
What this calculator does not account for
- Compact-stranded conductors (Chapter 9, Table 5A), bare conductors and multiconductor cables, which use their own dimensions.
- Conduit types not listed here, such as rigid fiberglass (RTRC), Type A and Type EB PVC and LFNC-A or LFNC-C.
- Jamming of three conductors, pulling tension, bend radius and the number of bends between pull points.
- Ampacity adjustment for the number of current-carrying conductors. Use the wire size calculator for that.
The installed design must follow the code edition your jurisdiction has adopted, its local amendments, and the authority having jurisdiction. Check every value in your own code book.
How to calculate conduit fill
To size a conduit, add up the area of every conductor in it (from Chapter 9, Table 5 for its insulation type and size), then find the smallest trade size whose allowed area in Chapter 9, Table 4 is at least that total. The allowed area depends on how many conductors there are: 53 percent of the raceway for one conductor, 31 percent for two, 40 percent for more than two, and 60 percent for a nipple of 24 inches or less.
Allowable fill percentage (Chapter 9, Table 1)
Before sizing a raceway you need to know how much of its inside area the conductors may occupy.
Where to look
Chapter 9, Table 1 and the Notes to Tables that follow it:
- one conductor or cable: 53 percent;
- two: 31 percent;
- more than two: 40 percent.
Note 3: equipment grounding and bonding conductors are counted. Note 4: a nipple not over 24 in. long between boxes or cabinets may be filled to 60 percent, and the ampacity adjustment factors do not apply to it. Note 9: a multiconductor cable counts as one conductor. Table 4 then gives each raceway's area at each percentage, so you rarely multiply by hand.
Procedure
- Count the conductors and cables, including EGCs (a multiconductor cable is one).
- Is it a nipple of 24 in. or less? If so, 60 percent.
- Otherwise read Table 1 for the count.
- In Table 4, read the column for that percentage and the trade size.
Worked example
Four conductors in a 1-in. EMT run 40 ft long.
- More than two conductors, not a nipple: 40 percent.
- Table 4, EMT, 1 in., 40 percent column: 0.346 in.².
Most common mistake
Using 40 percent for two conductors, and forgetting the 60 percent nipple rule or applying it to a long run.
Conductor area for raceway fill (Chapter 9, Table 5)
Conduit fill is worked in square inches, so every conductor's area, including its insulation, comes from one table.
Where to look
Chapter 9, Table 5. It is grouped by insulation type; find the group heading that lists your type, then the size row, and read the approximate area in in.² (the mm² column and the diameter columns sit beside it). Watch the groups: THHN, THWN and THWN-2 share the thinnest-insulation group; THW, THHW, TW and THW-2 are in a thicker group; XHHW has its own. Note 10 says the values are for concentric stranded conductors; compact conductors are in Table 5A. Bare conductors use Table 8.
Procedure
- Identify the insulation type and size.
- Find the right group in Table 5.
- Read the in.² area; multiply by the number of conductors of that kind.
- Add the groups together for a total.
Worked example
Area of three 6 AWG THWN conductors?
- THWN is in the THHN group; 6 AWG = 0.0507 in.².
- 3 × 0.0507 = 0.1521 in.².
Most common mistake
Reading the THW row for THWN (the names look alike but the THW insulation is thicker), or reading the diameter column instead of the area.
Sizing a raceway for mixed conductor sizes
Most real raceways carry different sizes, so you total the areas and then find the smallest trade size big enough.
Where to look
Chapter 9: Table 5 for each conductor's area, Table 1 for the percentage, and Table 4 for the raceway. Table 4 has a separate section for each raceway type (EMT, RMC, PVC and so on), with columns already worked out for 40, 60, 53 and 31 percent plus the total area. Note 6 sends mixed sizes to Tables 5 and 4. Count the EGC (Note 3).
Procedure
- Area of each conductor type × quantity, from Table 5.
- Add them for the total.
- Pick the percentage (normally 40 percent for more than two).
- In Table 4, for the raceway type, go down that column to the first value at least the total.
Worked example
Three 4 AWG THHN and one 8 AWG THHN EGC in EMT.
- 3 × 0.0824 = 0.2472; plus 0.0366 = 0.2838 in.².
- EMT, 40 percent: ¾ in. = 0.213 (too small); 1 in. = 0.346.
- Answer: 1-in. EMT.
Most common mistake
Reading the wrong raceway section in Table 4 (RMC and EMT differ), reading the total-area column, or leaving the EGC out.
Sections to look up
All in the 2026 NEC, with the 2023 number where it is different. Open your own book to each one; this page explains the rules in its own words and does not reproduce the code.
- Chapter 9, Table 1
- Chapter 9, Notes to Tables 1, 3, 4, 9
- Chapter 9, Table 5
- Chapter 9, Notes to Tables
- Chapter 9, Table 4
2023 NEC and 2026 NEC
Chapter 9, Table 4 names its sections by raceway in the 2026 NEC (for example "Chapter 9, Table 4 (EMT)") where the 2023 NEC named them by article number ("Article 358"). The fill percentages and the method are the same.
Every exam-relevant change from the 2023 to the 2026 NEC
Practice questions
Work each one with your code book open, then check the answer.
A 60-ft conduit run will contain four conductors (three phase conductors and an EGC). What maximum percentage of the conduit cross-section may they fill?
- A. 40%
- B. 53%
- C. 31%
- D. 60%
Show the answer to question 1
Answer: A. 40%
Chapter 9, Table 1: over two conductors, 40 percent. The EGC is counted (Note 3).
Reference: Chapter 9, Table 1; Note 3 (2026 NEC)
What is the approximate area of one 8 AWG THHN conductor in Chapter 9, Table 5?
- A. 0.0437 in.²
- B. 0.0507 in.²
- C. 0.0366 in.²
- D. 0.2160 in.²
Show the answer to question 2
Answer: C. 0.0366 in.²
Chapter 9, Table 5, THHN/THWN/THWN-2 group, 8 AWG: 0.0366 in.².
Reference: Chapter 9, Table 5 (2026 NEC)
Six conductors with a total area of 0.50 in.² are to be run in a 75-ft EMT run. What is the smallest trade size permitted?
- A. 1 in. EMT
- B. ¾ in. EMT
- C. 1¼ in. EMT
- D. 1½ in. EMT
Show the answer to question 3
Answer: C. 1¼ in. EMT
More than two conductors, so 40 percent. Table 4, EMT, 40 percent column: 1 in. = 0.346 (too small); 1¼ in. = 0.598. Answer: 1¼ in.
Reference: Chapter 9, Table 1; Chapter 9, Table 4 (2026 NEC)
A conduit will contain exactly two single conductors. What maximum percentage of its cross-section may they fill?
- A. 40%
- B. 53%
- C. 31%
- D. 60%
Show the answer to question 4
Answer: C. 31%
Chapter 9, Table 1: two conductors or cables, 31 percent.
Reference: Chapter 9, Table 1 (2026 NEC)
Common questions
What is the 40 percent rule for conduit fill?
Chapter 9, Table 1 lets conductors fill 40 percent of a conduit's internal area when there are more than two of them, 31 percent for two and 53 percent for one. The lower figures for two conductors keep them from jamming side by side in the pipe.
Does the ground wire count in conduit fill?
Yes. Equipment grounding and bonding conductors count toward fill at their actual area (Chapter 9, Note 3). They do not count as current-carrying conductors for ampacity adjustment.
How many 12 AWG THHN wires fit in 3/4-inch EMT?
16, using the 40 percent area of 3/4-inch EMT in Chapter 9, Table 4 and the area of 12 AWG THHN in Table 5. In 1/2-inch EMT the number is 9.
How many 10 AWG THHN fit in 1-inch PVC?
15 in 1-inch Schedule 40 PVC, from the same two tables. Schedule 80 has a smaller inside diameter, so it holds fewer.
How full can a short nipple be?
A nipple 24 inches or shorter between boxes or enclosures may be filled to 60 percent, and the conductors in it need no ampacity adjustment for bundling (Chapter 9, Note 4).
Is a conduit fill chart the same as this calculator?
A fill chart (Annex C of the NEC) gives the most conductors of one type and size for each conduit. This calculator does the same arithmetic from Chapter 9, Tables 4 and 5 and also handles mixed sizes and insulation types in one conduit, which a chart cannot.
Next step
Test yourself across the whole exam, or see how the course teaches a skill from the start. The course teaches this topic with the rest of the exam: a starting assessment finds what you need, each skill starts with a lesson, and review and timed practice exams check that it stays with you.
Other electrical calculators
- Voltage drop calculator
- Ohm's law calculator
- Wire size calculator
- Residential load calculator
- Box fill calculator
Other exam topics
Last verified November 11, 2026.