Where GFCI and AFCI protection is required

GFCI protection is required for receptacles in the locations listed in 210.8: in dwelling units, 210.8(A) covers bathrooms, garages, outdoors, basements, kitchens, laundry areas, areas within 6 feet of a sink and the other listed locations; outside dwellings, 210.8(B) has its own list. AFCI protection is required in dwelling units for 120-volt, 15- and 20-ampere branch circuits supplying the rooms listed in 210.12(B), such as bedrooms, living rooms, kitchens, hallways and laundry areas. A kitchen or laundry circuit often needs both.

GFCI receptacles in dwelling units (210.8(A))

What the rule is for
In a dwelling unit, every 125-volt through 250-volt receptacle on a single-phase branch circuit rated 150 volts or less to ground needs GFCI protection when it is in a listed location. There is no ampere limit in (A), so a 240-volt, 50-ampere garage receptacle is covered. The 2026 list has 14 items: bathrooms; garages; storage or work areas of accessory buildings; outdoors; crawl spaces at or below grade; basements; kitchens; areas with a sink and permanent provisions for food or beverage preparation or cooking; within 6 feet of the top inside edge of a sink bowl; boathouses; within 6 feet of the outside edge of a bathtub or shower stall; laundry areas; indoor damp locations; and indoor wet locations. Basements are listed without the word "unfinished," so a finished basement counts. Four exceptions follow the list; on the exam, ignore them unless the question names one.

How to find it
Chapter 2, Article 210, Part I, 210.8(A) "Dwelling Units". Read the opening sentence for voltage and phase limits, then scan the numbered list.

Worked lookup
A 125-volt receptacle is installed in a dwelling crawl space that is at grade level, to serve a dehumidifier. Does it need GFCI protection? 210.8(A)(5) lists crawl spaces at or below grade level. Answer: yes, per 210.8(A)(5).

Common trap
Using the "unfinished" wording that belongs to 210.8(B) for other occupancies, or assuming 240-volt receptacles are exempt. Also remember distances use the cord path described in the 210.8 opening paragraph.

GFCI receptacles outside dwelling units (210.8(B))

What the rule is for
Outside dwelling units, GFCI protection covers two groups of receptacles in the listed locations: 125-volt through 250-volt receptacles on single-phase circuits rated 150 volts or less to ground and 50 amperes or less, and all receptacles on three-phase circuits rated 150 volts or less to ground and 100 amperes or less. A 480Y/277-volt receptacle is 277 volts to ground, so it is outside the rule. The 2026 list has 16 items, including bathrooms, kitchens, buffet serving areas, rooftops, outdoors, within 6 feet of a sink, indoor damp and wet locations, locker rooms with showers, garages and service bays (not showrooms or exhibition halls), crawl spaces at or below grade, unfinished areas of basements, within 6 feet of aquariums and bait wells, laundry areas, and within 6 feet of tubs and showers. Five exceptions follow, such as industrial assured grounding programs and industrial laboratories.

How to find it
Chapter 2, Article 210, Part I, 210.8(B) "Other Than Dwelling Units". Check the opening sentence for the voltage, phase and ampere limits before reading the list.

Worked lookup
A restaurant kitchen has a 208Y/120-volt, three-phase, 60-ampere receptacle for a mixer. Does it need GFCI protection? 210.8(B): three-phase, 120 volts to ground, 60 amperes is within 100 amperes, and (2) lists kitchens. Answer: yes, per 210.8(B)(2).

Common trap
Using the dwelling list. In other occupancies only unfinished basement areas are listed, and showrooms are excluded from the garage item. Also do not stop at single-phase; three-phase receptacles up to 100 amperes are covered.

AFCI protection in dwelling units (210.12(B))

What the rule is for
In a dwelling unit, every 120-volt, single-phase, 10-, 15- or 20-ampere branch circuit that supplies outlets or devices in the listed rooms needs AFCI protection by one of the methods in 210.12(A). The 2026 list is kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas and similar areas. Bathrooms, garages and outdoors are not on the dwelling list. A 240-volt circuit is not covered, and neither is a circuit above 20 amperes. Two exceptions cover an individual fire alarm circuit in metal wiring methods and an individual circuit for arc welding equipment. The AFCI itself must be listed and readily accessible. AFCI and GFCI are separate requirements, so a kitchen or laundry circuit often needs both.

How to find it
Chapter 2, Article 210, Part I, 210.12 "Arc-Fault Circuit-Interrupter Protection", then (B) "Dwelling Units". The methods are in (A), dormitories in (C), other occupancies in (D), and extensions in (E).

Worked lookup
A dwelling 120-volt, 15-ampere circuit supplies the receptacles in a den. Does it need AFCI protection? 210.12(B): 120-volt, single-phase, 15 amperes, and (7) lists dens. Answer: yes, per 210.12(B)(7).

Common trap
Adding bathrooms or garages to the dwelling AFCI list, or confusing the AFCI list with the GFCI list in 210.8(A). The other trap is forgetting the 10-ampere circuits that 2026 now names alongside 15 and 20 amperes.

Sections to look up

All in the 2026 NEC, with the 2023 number where it is different. Open your own book to each one; this page explains the rules in its own words and does not reproduce the code.

2023 NEC and 2026 NEC

210.8(F), GFCI for outdoor outlets, covers outlets rated 60 amperes or less in the 2026 NEC, a higher limit than in 2023, and adds an exception that lets listed HVAC equipment use a Class C special-purpose GFCI.

The welder exemption in 210.12(B) has no expiry date in the 2026 NEC and also applies in garages and accessory buildings.

Replacing a receptacle where GFCI protection is required: the 2026 exception that allows a non-GFCI replacement of the same type (406.12(D), which was 406.4(D)(3)) applies only if the box is too small, no box upstream can take a GFCI, and a GFCI breaker cannot provide the protection.

Every exam-relevant change from the 2023 to the 2026 NEC

Practice questions

Work each one with your code book open, then check the answer.

  1. A 125-volt, 20-ampere receptacle is installed in the family room of a finished basement in a single-family dwelling. Does 210.8(A) require GFCI protection?

    • A. No, because only unfinished basements are listed
    • B. No, because family rooms are not on the list
    • C. Yes, because 210.8(A) lists basements without regard to finish
    • D. Only if a sink is within 6 ft
    Show the answer to question 1

    Answer: C. Yes, because 210.8(A) lists basements without regard to finish

    210.8(A)(6) lists basements for dwelling units with no finished or unfinished qualifier, so this receptacle needs GFCI protection.

    Reference: 210.8(A)(6) (2026 NEC)

  2. Outside dwelling units, 210.8(B) covers single-phase 125-volt through 250-volt receptacles on circuits rated 150 volts or less to ground and up to what ampere rating?

    • A. 60 A
    • B. 50 A
    • C. 100 A
    • D. 20 A
    Show the answer to question 2

    Answer: B. 50 A

    210.8(B) covers single-phase receptacles of 125 volts through 250 volts on circuits rated 150 volts or less to ground and 50 amperes or less, and three-phase receptacles up to 100 amperes.

    Reference: 210.8(B) (2026 NEC)

  3. A dwelling 120-volt, 20-ampere branch circuit supplies the receptacles in two bedrooms. Does 210.12(B) require AFCI protection?

    • A. No, because 20-ampere circuits are not covered
    • B. No, because receptacles need only GFCI
    • C. Yes
    • D. Only for new construction with sleeping rooms over 70 sq ft
    Show the answer to question 3

    Answer: C. Yes

    210.12(B) covers 120-volt, single-phase, 10-, 15- and 20-ampere circuits supplying outlets or devices in dwelling bedrooms, among other rooms.

    Reference: 210.12(B) (2026 NEC)

  4. In a dwelling laundry area, a 240-volt, 30-ampere single-phase receptacle serves the clothes dryer on a 120/240-volt system. Does 210.8(A) require GFCI protection for it?

    • A. No, because 210.8(A) covers only 125-volt receptacles
    • B. Yes, because it is a 125-volt through 250-volt receptacle in a laundry area on a circuit of 150 volts or less to ground
    • C. No, because 210.8(A) covers only 15- and 20-ampere receptacles
    • D. No, because the circuit is 240 volts to ground
    Show the answer to question 4

    Answer: B. Yes, because it is a 125-volt through 250-volt receptacle in a laundry area on a circuit of 150 volts or less to ground

    210.8(A) covers 125-volt through 250-volt receptacles on single-phase circuits rated 150 volts or less to ground, and (12) lists laundry areas. A 120/240-volt system is 120 volts to ground.

    Reference: 210.8(A)(12) (2026 NEC)