Free calculator · 2026 and 2023 NEC
Wire Size Calculator
Enter the load and the conditions and get the smallest copper or aluminum wire and its breaker size under NEC Table 310.16, with continuous loads at 125 percent, temperature correction, derating for more than three conductors and the terminal temperature limit, each check shown.
8 AWG copper, 90°C insulation, on a 40 A breaker or fuse
The next size down, 10 AWG, fails because its 60°C terminal ampacity is under the 40 A needed.
How it was worked out
- Load: 0 A noncontinuous + 125% of 32 A continuous = 40 A (210.19(A)). The breaker or fuse must be at least this: the next standard rating is 40 A (240.6(A)).
- Terminals: not marked otherwise, so a circuit rated 100 A or less uses the 60°C column (110.14(C)). 8 AWG copper is 40 A at 60°C, at least 40 A.
- Correction for 86°F in the 90°C column: 1 (Table 310.15(B)(1)(1)). 3 current-carrying conductors: no adjustment.
- Derated ampacity: 55 A (90°C column, Table 310.16) × 1 = 55 A, at least the 32 A load.
- The derated 55 A is more than the 40 A the 60°C terminals allow, so the conductor's usable ampacity is 40 A. A higher-rated insulation helps with derating but never raises the terminal limit.
- Protection: usable ampacity 40 A; a 40 A device does not exceed it.
Code sections (2026 NEC): 210.19(A); 210.20(A); 110.14(C); Table 310.16; Table 310.15(B)(1)(1); Table 310.15(C)(1); 240.4; 240.4(D); 240.6(A).
Practice this on exam-style questions
Ampacity, derating and terminal-rating questions turn up all through the journeyman exam. Practice them in a free practice test for your state.
AmpPrep courses teach conductor sizing and derating for each state's journeyman exam, with lessons, review and timed practice exams. Find your state's exam.
What this calculator does not account for
- The rooftop temperature adder, and which neutral and grounding conductors count as current-carrying: enter the count you have worked out.
- Dwelling services and feeders sized at 83 percent (310.12), motor and air-conditioning circuits (Articles 430 and 440), and parallel conductors.
- Cable types with their own limits, such as Type NM at the 60°C ampacity, and the ampacity tables other than Table 310.16.
- The next-size-up rule does not apply to a branch circuit with more than one receptacle for cord-and-plug loads.
- Voltage drop on long runs. Use the voltage drop calculator for that.
The installed design must follow the code edition your jurisdiction has adopted, its local amendments, and the authority having jurisdiction. Check every value in your own code book.
How to size wire: ampacity and derating
To size a conductor, start from its ampacity in Table 310.16 in the column for its insulation temperature, then adjust: multiply by the ambient temperature correction factor when the surrounding air is not 30°C (86°F), and by the adjustment factor when more than three current-carrying conductors share a raceway or cable. The adjusted ampacity must carry the load, and the final size is also checked against the temperature rating of the terminals.
Reading Table 310.16
Table 310.16 is the table you will open most on the exam. It gives the ampacity of insulated conductors with no more than three current-carrying conductors in a raceway or cable, at a 30°C (86°F) ambient.
Where to look
Article 310, section 310.16, Table 310.16. The left half is copper; the right half is aluminum or copper-clad aluminum. Each half has three columns: 60°C, 75°C and 90°C. The insulation types belonging to each column are printed at the top of the column. If an insulation has different ratings for wet and dry locations (for example XHHW or THWN-2), Table 310.4(1) gives the rating for each.
Procedure
- Copper unless the question says aluminum.
- Find the insulation type's temperature column.
- Go down to the conductor size row and read the ampacity.
- Reverse problem (size for a load): go down the right column until the first ampacity that is at least the load.
Worked example
What is the ampacity of 1/0 AWG THWN copper?
- THWN appears at the top of the copper 75°C column.
- Row 1/0 AWG, 75°C column: 150 A.
Most common mistake
Reading the wrong column. THHN is a 90°C insulation, THWN is 75°C, and TW is 60°C. Reading the aluminum half by accident is the second classic mistake. Read the column header every time. (Whether the final ampacity may use that column also depends on the terminations, which is the next skill.)
Correcting ampacity for ambient temperature
Table 310.16 assumes the air around the conductors is 30°C (86°F). Hotter air means the conductor cannot shed heat as well, so its ampacity must be reduced. Cooler air allows a little more.
Where to look
Article 310, 310.15(B), Table 310.15(B)(1)(1), "based on 30°C". It is the one to use with Table 310.16. Rows are ambient temperature ranges, in °C on the left and °F on the right. The columns are the conductor's temperature rating: 60°C, 75°C, 90°C. (The second table, based on 40°C, goes with Tables 310.18 to 310.21 and is not used with 310.16.)
Procedure
- Get the ampacity from Table 310.16 in the column for the insulation.
- In Table 310.15(B)(1)(1), find the row for the ambient. Use the °F scale if the ambient is given in °F; do not convert.
- Read the factor in the SAME temperature column you used in step 1.
- Multiply: corrected ampacity = table ampacity × factor.
Worked example
4 AWG THHN copper in a 42°C room.
- Table 310.16, 90°C column: 95 A.
- Table 310.15(B)(1)(1), row 41–45°C, 90°C column: 0.87.
- 95 × 0.87 = 82.7 A.
Most common mistake
Mixing columns, for example taking the 90°C ampacity and multiplying it by the 75°C factor. The factor column must match the ampacity column. Dividing by the factor instead of multiplying is the other common slip; a factor below 1 must make the ampacity smaller.
Adjusting for more than three current-carrying conductors
Table 310.16 assumes no more than three current-carrying conductors (CCCs) together. When more share a raceway or cable for more than 24 in., each one heats the others, so every conductor's ampacity is reduced by a percentage.
Where to look
Article 310, 310.15(C)(1), Table 310.15(C)(1). The left column is the number of conductors (in bands: 4–6, 7–9, 10–20 and so on); the right column is the percentage of the Table 310.16 value. Read the footnote: spares are counted, and the count follows 310.15(E) and (F) (the previous skill).
Procedure
- Count the CCCs correctly (neutrals only when they count, never EGCs, include spares).
- Find the band for that count in Table 310.15(C)(1) and turn the percentage into a decimal (80 percent = 0.80).
- Get the ampacity from Table 310.16 for the insulation column.
- Multiply: adjusted ampacity = table ampacity × decimal.
- To size a conductor: divide the required ampacity by the decimal, then find the first table value at least that large.
Worked example
Six current-carrying 10 AWG THHN copper conductors in one conduit.
- 6 falls in the 4–6 band; Table 310.15(C)(1) gives 80 percent.
- Table 310.16, 10 AWG copper, 90°C: 40 A.
- 40 × 0.80 = 32 A per conductor.
Most common mistake
Landing in the wrong band. Four conductors is already "more than three", so 4 gets the first reduction; do not skip it. Also, the percentage multiplies the ampacity; it is never subtracted from it.
Putting it together: correction, adjustment, terminals
Real questions combine a hot room, a full conduit, and terminals that limit the column. 310.15(A) allows the correction and adjustment factors to be applied to the ampacity for the conductor's own temperature rating, as long as the result does not exceed the termination ampacity under 110.14(C). That is why 90°C wire is useful even on 75°C or 60°C terminals.
Procedure
- Start with the Table 310.16 ampacity in the INSULATION column (90°C for THHN).
- Multiply by the ambient factor from Table 310.15(B)(1)(1), same column.
- Multiply by the adjustment percentage from Table 310.15(C)(1).
- Separately, look up the TERMINATION-column ampacity (110.14(C): 60°C for 100 A or less unless marked; 75°C over 100 A).
- The allowable ampacity is the SMALLER of step 3 and step 4.
Worked example
Six current-carrying 8 AWG THHN copper conductors, 40 A circuits, ambient 38°C, unmarked terminals.
- Table 310.16, 8 AWG copper, 90°C: 55 A.
- Ambient row 36–40°C, 90°C column: 0.91.
- 6 conductors → 80 percent.
- 55 × 0.91 × 0.80 = 40.04 A.
- Terminals: 40 A circuit, unmarked → 60°C → 8 AWG = 40 A.
- Allowable = smaller of 40.04 A and 40 A = 40 A.
Most common mistake
Starting the derating from the termination column (for example 75°C) instead of the insulation column, which throws away the extra capacity of 90°C wire. The opposite error, stopping at the derated 90°C value without checking the terminal limit, is just as common.
Sections to look up
All in the 2026 NEC, with the 2023 number where it is different. Open your own book to each one; this page explains the rules in its own words and does not reproduce the code.
- 310.14
- 310.15
- 310.16
- Table 310.16
- Table 310.4(1)
- Table 310.15(B)(1)(1)
- Table 310.15(C)(1)
- 110.14
2023 NEC and 2026 NEC
The 2026 NEC lowers the smallest general-wiring conductors to 16 AWG copper and 14 AWG copper-clad aluminum (aluminum stays 12 AWG), in 310.5, which was 310.3 in the 2023 NEC.
Table 310.16 in the 2026 NEC adds values for 16 AWG copper and a row for 14 AWG copper-clad aluminum, neither of which is in the 2023 table. The 14 AWG through 500 kcmil values compared in both editions match.
Every exam-relevant change from the 2023 to the 2026 NEC
Practice questions
Work each one with your code book open, then check the answer.
What is the ampacity in Table 310.16 of 4 AWG THWN copper?
- A. 70 A
- B. 95 A
- C. 65 A
- D. 85 A
Show the answer to question 1
Answer: D. 85 A
THWN is listed in the 75°C column. Table 310.16 gives 85 A for 4 AWG copper at 75°C.
Reference: Table 310.16 (2026 NEC)
6 AWG THWN copper conductors are installed where the ambient temperature is 40°C. What is their corrected ampacity? Round to 0.1 A.
- A. 57.2 A
- B. 59.2 A
- C. 53.3 A
- D. 73.9 A
Show the answer to question 2
Answer: A. 57.2 A
THWN, so 75°C. Table 310.16 gives 65 A for 6 AWG copper at 75°C. Table 310.15(B)(1)(1), row 36–40°C, 75°C column: 0.88. 65 × 0.88 = 57.2 A.
Reference: 310.15(B); Table 310.15(B)(1)(1); Table 310.16 (2026 NEC)
Eight current-carrying 12 AWG THHN copper conductors share a conduit. Using the 90°C column, what is the adjusted ampacity of each? Round to 0.1 A.
- A. 15.0 A
- B. 24.0 A
- C. 21.0 A
- D. 17.5 A
Show the answer to question 3
Answer: C. 21.0 A
8 conductors, so 7–9 band, so Table 310.15(C)(1) gives 70 percent. Table 310.16, 12 AWG copper, 90°C: 30 A. 30 × 0.70 = 21.0 A.
Reference: 310.15(C)(1); Table 310.15(C)(1); Table 310.16 (2026 NEC)
Four current-carrying 6 AWG THHN copper conductors share a conduit in a 35°C ambient. They serve 50 A circuits with unmarked terminals. What is the allowable ampacity of each conductor? Round to 0.1 A.
- A. 57.6 A
- B. 55.0 A
- C. 40.0 A
- D. 75.0 A
Show the answer to question 4
Answer: B. 55.0 A
Insulation column: Table 310.16, 6 AWG copper, 90°C = 75 A. Ambient 31–35°C, 90°C column: 0.96. 4 conductors, so 80 percent. 75 × 0.96 × 0.80 = 57.6 A. Terminals: 50 A circuit, unmarked, so 60°C, so 6 AWG = 55 A. Allowable = smaller = 55.0 A.
Reference: 310.15(A); 110.14(C)(1)(a); Table 310.16; Table 310.15(B)(1)(1); Table 310.15(C)(1) (2026 NEC)
Common questions
What size wire do I need for 20, 30, 40 and 50 amps?
For copper with 60°C terminals (the rule for unmarked equipment on circuits of 100 A or less) and no derating: 20 A takes 12 AWG, 30 A takes 10 AWG, 40 A takes 8 AWG and 50 A takes 6 AWG. A load that runs for three hours or more needs 125 percent of its current, so a 32 A continuous load needs a 40 A circuit and wire.
What size wire for 60 amps?
With copper and 60°C terminals, 4 AWG. If the breaker and the equipment are listed and marked for 75°C, 6 AWG.
What does wire derating mean?
Table 310.16 assumes 30°C (86°F) air and no more than three current-carrying conductors together. Hotter air lowers a conductor's ampacity by the factor in Table 310.15(B)(1)(1), and more than three current-carrying conductors in one raceway or cable lower it again by the percentage in Table 310.15(C)(1). Both factors multiply.
Can I use the 90°C column for THHN?
For derating, yes: start from the 90°C ampacity and apply the correction and adjustment factors. But the result can never be more than the ampacity in the column of the lowest-rated terminal, usually 60°C or 75°C (110.14(C)). The calculator checks both.
What is a continuous load?
A load whose maximum current is expected to continue for three hours or more, such as store lighting or a water heater. Conductors and breakers for it are sized at 125 percent of that current unless the equipment is listed for 100 percent operation.
Why does 12 AWG copper go on a 20 A breaker when the table says 25 A?
The small-conductor rule in 240.4(D) caps the breaker or fuse for 14, 12 and 10 AWG copper at 15, 20 and 30 A, whatever the table ampacity, and for 12 and 10 AWG aluminum at 15 and 25 A.