Grounding and bonding conductor sizing
Each grounding conductor is sized from a different table. An equipment grounding conductor (EGC) is sized from the rating of the breaker or fuse ahead of it, in Table 250.122. A grounding electrode conductor (GEC) is sized from the largest service conductor, in Table 250.66. Main, system and supply-side bonding jumpers are sized from the supply conductors, in Table 250.102(C)(1). Picking the right table is most of the answer.
Sizing the equipment grounding conductor (Table 250.122)
The wire-type equipment grounding conductor (EGC) must carry fault current long enough for the breaker or fuse to open, so it is sized from the device ahead of it, not from the load.
Where to look
Article 250, 250.122 and Table 250.122. Each row is an overcurrent device rating "not exceeding" that value; read the copper or the aluminum/copper-clad aluminum column. 250.122(A): the EGC never has to be larger than the circuit conductors. 250.102(D): an equipment bonding jumper on the load side of a device is sized the same way.
Procedure
- Find the rating of the breaker or fuse protecting the circuit (calculate it first if needed).
- Go down the first column to the first row equal to or greater than that rating.
- Read the copper column unless the question says aluminum.
Worked example
A feeder is protected by a 150-A breaker. Copper EGC?
- 150 A is more than 100 and not more than 200, so the 200-A row applies.
- Copper column: 6 AWG.
Most common mistake
Sizing from the load current or the conductor ampacity instead of the device rating. Using the supply-side table (Table 250.102(C)(1), based on conductor size) for an EGC is the other.
Sizing the grounding electrode conductor
The grounding electrode conductor (GEC) connects the service to the earth electrodes. It is sized from the service conductors, not from the load.
Where to look
Article 250 Part III, 250.66 and Table 250.66. Find the row for the largest ungrounded service conductor (copper or aluminum column) and read the GEC size. Note 1: for parallel sets, add the areas of one conductor from each set. Then the limits: (A) a GEC that goes only to rods, pipes or plates need not be larger than 6 AWG copper; (B) only to concrete-encased electrodes, not larger than 4 AWG copper; (C) to a ground ring, not larger than the ring conductor.
Procedure
- Identify the largest ungrounded conductor, or add the parallel sets.
- Read the table row in the right metal column.
- If the GEC runs only to one electrode type with a limit, apply it.
Worked example
Two sets of 250 kcmil copper; GEC to the water pipe.
- 2 × 250 = 500 kcmil → "over 350 through 600" → 1/0 AWG copper.
- No limit applies to a water pipe.
Most common mistake
Sizing from one conductor of a parallel set, or forgetting that a GEC running only to ground rods stops at 6 AWG copper.
Main, system and supply-side bonding jumpers
Bonding jumpers on the supply side must carry fault current back to the source, so they are sized from the supply conductors.
Where to look
Article 250: 250.28(D) for main and system bonding jumpers and 250.102(C) for supply-side jumpers. Both use Table 250.102(C)(1). Its rows look like the GEC table up to 1100 kcmil copper (1750 kcmil aluminum). Above that, Note 1 applies: the jumper must be at least 12.5 percent of the area of the largest conductor or the parallel equivalent. Note 2: it never needs to be larger than the ungrounded conductors. For parallel runs in separate raceways (250.102(C)(2)), size one jumper per raceway from the conductors in it, or one jumper for all raceways from the sum of the areas. Chapter 9 Table 8 gives the areas of AWG sizes.
Procedure
- Find the largest conductor, or the sum of areas for parallel sets.
- Up to 1100 kcmil Cu: read the table.
- Above: multiply by 0.125 and pick the smallest size with at least that area.
Worked example
Four sets of 500 kcmil Cu, one jumper.
- 4 × 500 = 2000 kcmil; 12.5 percent = 250 kcmil.
- Jumper: 250 kcmil Cu.
Most common mistake
Using the 3/0 maximum from the GEC table for a large service. Bonding jumpers keep growing with the 12.5 percent rule.
Sections to look up
All in the 2026 NEC, with the 2023 number where it is different. Open your own book to each one; this page explains the rules in its own words and does not reproduce the code.
- 250.122
- Table 250.122
- 250.102(D)
- 250.66
- Table 250.66
- 250.28(D)
- 250.102(C)
- Table 250.102(C)(1)
2023 NEC and 2026 NEC
250.122 is relettered in the 2026 NEC: increases in size are (D), multiple circuits (E), motor circuits (F), cords (G), parallel runs (H) and feeder taps (I). The sizing rules are the same, but a 2026 parallel run caps each raceway's EGC at the size of the largest ungrounded conductor in that raceway.
Every exam-relevant change from the 2023 to the 2026 NEC
Practice questions
Work each one with your code book open, then check the answer.
A branch circuit is protected by a 90-A breaker. What is the minimum size copper equipment grounding conductor?
- A. 8 AWG
- B. 10 AWG
- C. 6 AWG aluminum
- D. 6 AWG
Show the answer to question 1
Answer: A. 8 AWG
Table 250.122: 90 A is over 60 A and not over 100 A, so the 100-A row applies. Copper: 8 AWG.
Reference: 250.122; Table 250.122 (2026 NEC)
The largest ungrounded service-entrance conductor is 3/0 AWG copper. What is the minimum copper grounding electrode conductor to a metal underground water pipe?
- A. 4 AWG
- B. 2 AWG
- C. 6 AWG
- D. 8 AWG
Show the answer to question 2
Answer: A. 4 AWG
Table 250.66, copper, "2/0 or 3/0", so 4 AWG copper.
Reference: 250.66; Table 250.66 (2026 NEC)
A service has 250 kcmil copper ungrounded conductors in one raceway. What is the minimum size of a copper main bonding jumper?
- A. 4 AWG
- B. 1/0 AWG
- C. 2 AWG
- D. 6 AWG
Show the answer to question 3
Answer: C. 2 AWG
250.28(D)(1) sends you to Table 250.102(C)(1). 250 kcmil Cu is "over 3/0 through 350", so 2 AWG copper.
Reference: 250.28(D); 250.102(C); Table 250.102(C)(1) (2026 NEC)
A feeder is protected by a 400-A fuse. What is the minimum size copper equipment grounding conductor?
- A. 4 AWG
- B. 2 AWG
- C. 3 AWG
- D. 1 AWG aluminum
Show the answer to question 4
Answer: C. 3 AWG
Table 250.122, 400-A row, copper column: 3 AWG.
Reference: 250.122; Table 250.122 (2026 NEC)
Next step
Test yourself across the whole exam, or see how the course teaches a skill from the start. The course teaches this topic with the rest of the exam: a starting assessment finds what you need, each skill starts with a lesson, and review and timed practice exams check that it stays with you.